Bonding Jumper

If you are using the tray as an equipment ground as classified by UL, you must use a bonding jumper (one only with Series 6 single piece construction) for bridging adjustable splice plates and runs that aren't connected or across expansion joints.

- For steel trays use a 200 Amp Jumper. This provides a 100 Amp equipment ground through 18" width tray, and a 200 Amp ground on 24" wide tray.

- For aluminum trays use a 600 Amp jumper to 18" widths and two 600 Amp jumpers to provide 1000 Amp ground for 24" wide tray. For 64A24010 and 66A24010 tray you get 1200 Amp ground.

Type Name Pack pcs.
Weight
lb/100pc
Sku
9CBJ200
Bonding Jumper, Cable Size #6, Rated Amps 200. 9CBJ200
9CBJ600
Bonding Jumper, Cable Size #1, Rated Amps 600. 9CBJ600